Abstract
Metal-oxide surge arresters play an important role in protecting power system equipment doing lightning surges and switching surges. Especially, overhead transmission lines are often struck by lightning. This often results in line faults. These can be reduced effectively by installing lightning arresters. Recently, some simulation programs such as EMTP/ATP have been developed to estimate the benefits of the installation of lightning arresters. For those simulation programs, the arrester model is usually a non-linear resistor. As seen in many discussions from papers and theories, the ZnO arrester, which is the most popular, has the dynamic behavior of frequency dependence. In other words, the residual voltage of the arrester depends on the frequency of surge. The higher the frequency of surges, the higher the residual voltage of the arrester. In this article, the simulation results of four different frequency-dependent models examined by EMTP/ATP show relative maximum error lower than 9%, as well as the residual voltage of arrester being increased by 14% when the front time of surge is reduced from 8 to 1 µs. With these results, this article offers suggestions to use frequency-dependent arrester models for all corrective arrester simulations to enhance the accuracy of simulation programs.