Analysis of Metal Oxide Varistor Arresters for Protection of Multiconductor Transmission Lines Using Unconditionally-Stable Crank–Nicolson FDTD
Open Access
Abstract
Surge arresters may represent an efficient choice for limiting lightning surge effects, significantly reducing the outage rate of power lines. The present work firstly presents an efficient numerical approach suitable for insulation coordination studies based on an implicit Crank–Nicolson finite difference time domain method; then, the IEEE recommended surge arrester model is reviewed and implemented by means of a local implicit scheme, based on a set of non-linear equations, that are recast in a suitable form for efficient solution. The model is proven to ensure robustness and second-order accuracy. The implementation of the arrester model in the implicit Crank–Nicolson scheme represents the added value brought by the present study. Indeed, its preserved stability for larger time steps allows reducing running time by more than compared to the well-known finite difference time domain method based on the explicit leap-frog scheme. The reduced computation time allows faster repeated solutions, which need to be looked for on assessing the lightning performance (randomly changing, parameters such as peak current, rise time, tail time, location of the vertical leader channel, phase conductor voltages, footing resistance, insulator strength, etc. would need to be changed thousands of times).
Keywords
This publication has 53 references indexed in Scilit:
- Modelling of metal oxide arrester for very fast transientsIET Science, Measurement & Technology, 2011
- A Review of Current Issues in State-of-Art of Wind Farm Overvoltage ProtectionEnergies, 2011
- Potential distribution analysis of suspended-type metal-oxide surge arrestersIEEE Transactions on Power Delivery, 2003
- Direct time-domain analysisof transmission lines above a lossy groundIEE Proceedings - Science, Measurement and Technology, 2001
- A simplified model for zinc oxide surge arrestersIEEE Transactions on Power Delivery, 1999
- Influence of a lossy ground on lightning-induced voltages on overhead linesIEEE Transactions on Electromagnetic Compatibility, 1996
- Finite-difference, time-domain analysis of lossy transmission linesIEEE Transactions on Electromagnetic Compatibility, 1996
- An unconditionally stable finite element time-domain solution of the vector wave equationIEEE Microwave and Guided Wave Letters, 1995
- Skin-effect considerations on transient response of a transmission line excited by an electromagnetic pulseIEEE Transactions on Electromagnetic Compatibility, 1992
- Experimental study of response of power distribution lines to direct lightning hitsIEEE Transactions on Power Delivery, 1989