Coordinated Priority-aware Charging of Distributed Batteries in Oversubscribed Data Centers
Authors:
- 1 October 2020
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 839-851
Abstract
Data centers employ batteries for uninterruptible operation during maintenance and power failures, for example, when switching to diesel generator power after a utility power failure. Depleted batteries start to recharge once the input power is back, creating a sudden power spike in the power hierarchy. If not properly controlled, a sustained power overload can potentially trip circuit breakers, leading to service outages. Power overloads due to battery recharging are even more likely in oversubscribed data centers where the power infrastructure is aggressively provisioned for high utilization. The problem caused by simultaneous recharging of batteries in a data center has not been extensively studied and no real-world solutions have been proposed in the literature.In this paper, we identify the problem due to battery recharging with case studies from Facebook's data centers. We describe the solutions we have developed to coordinate charging of batteries without exceeding the circuit breaker power limit. We explain in detail, the variable battery charging algorithm built into the distributed battery charger hardware deployed in Facebook data centers, and the system design considerations necessary on a large scale. The new variable charger is able to reduce battery recharge power by up to 80%. We further leverage individual battery charging control mechanism to coordinate the charging process such that we charge the batteries according to priorities of applications running on the servers supported by the batteries. We evaluate our coordinated priority-aware battery charging algorithm by building a prototype in a Facebook production data center as well as through simulation experiments using production power traces. Our results show that we are able to meet reliability service level agreements by using our battery recharging algorithm, while satisfying given power constraints.Keywords
This publication has 37 references indexed in Scilit:
- Comprehensive understanding of operation cost reduction using energy storage for IDCs2015
- Physics-based simulation of the impact of demand response on lead-acid emergency power availability in a datacenterJournal of Power Sources, 2015
- Underprovisioning backup power infrastructure for datacenters2014
- MultiGreen2013
- Aggressive Datacenter Power Provisioning with BatteriesACM Transactions on Computer Systems, 2013
- Using batteries to reduce the power costs of internet-scale distributed networks2012
- Energy storage in datacenters2012
- Leveraging stored energy for handling power emergencies in aggressively provisioned datacenters2012
- Towards realizing a low cost and highly available datacenter power infrastructure2011
- Power provisioning for a warehouse-sized computer2007