Robust decentralised design for multiple FACTS damping controllers
Authors:
- 1 January 1997
- journal article
- Published by Institution of Engineering and Technology (IET) in IEE Proceedings - Generation, Transmission and Distribution
- Vol. 144 (1) , 61-67
Abstract
A systematic robust decentralised design procedure based on the H∞-optimisation technique for tuning multiple FACTS devices is presented. The design procedure uses a model-matching robustness formulation and requires the design of a parameter to achieve decentralised control. The approach is used to design damping controllers for an SVC and a TCSC to enhance the damping of the interarea modes in a 3-area 6-machine system. The feedback signals for the controllers are synthesised from the local voltage and current measurements.Keywords
This publication has 9 references indexed in Scilit:
- Concepts for design of FACTS controllers to damp power swingsIEEE Transactions on Power Systems, 1995
- A robust frequency domain optimization technique for tuning series compensation damping controllersIEEE Transactions on Power Systems, 1995
- A parametrization approach to optimal H2 and H∞ decentralized control problemsAutomatica, 1993
- Robust control design of power system stabilizers using multivariable frequency domain techniquesInternational Journal of Robust and Nonlinear Control, 1992
- Design of reliable control systemsIEEE Transactions on Automatic Control, 1992
- A toolbox for power system dynamics and control engineering education and researchIEEE Transactions on Power Systems, 1992
- Simplifying theH∞ theory via loop-shifting, matrix-pencil and descriptor conceptsInternational Journal of Control, 1989
- State-space solutions to standard H/sub 2/ and H/sub infinity / control problemsIEEE Transactions on Automatic Control, 1989
- Excitation System Models for Power System Stability StudiesIEEE Transactions on Power Apparatus and Systems, 1981