Impact of the Inductive FCL on the Interrupting Characteristics of High-Voltage CBs During Out-of-Phase Faults
Authors:
- 22 September 2009
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 24 (4) , 2177-2185
Abstract
With respect to power systems installed with inductive fault current limiters (FCLs), the impact of an FCL on the out-of-phase fault current level was first analyzed, and thereby a method for determining the critical length of the power transmission tie lines was also given. Based on theoretical analysis and deduction, strict mathematical formulas were obtained to properly describe the relationship between the current limit factor and the recovery voltage of a circuit breaker (CB) as well as the rate of rise of recovery voltage (RRRV). Further, the concrete impacts of an FCL on the maximum and the RRRV of the recovery voltage were analyzed. Regarding out-of-phase faults, a conception of interruption severity as well as its quantitative expression for CBs was introduced, and a formula was established to incorporate the influence from the current limit factor and stray capacitance on the interruption severity of CBs, subsequently followed by detailed investigations. The aforementioned proposed research presents analytical methodology and practical reference for the parameter optimization of the inductive FCL and reliable selection of the interrupting characteristics of the high-voltage CBs.Keywords
This publication has 9 references indexed in Scilit:
- System Technology and Test of CURL 10, a 10 kV, 10 MVA Resistive High-Tc Superconducting Fault Current LimiterIEEE Transactions on Applied Superconductivity, 2005
- Improvement of power quality by means of fault current limitation2004
- Reduction of rating required for circuit breakers by employing series-connected fault current limitersIEE Proceedings - Generation, Transmission and Distribution, 2004
- Inductive type fault current limiter with Bi-2223 thick film on a MgO cylinderIEEE Transactions on Applied Superconductivity, 2003
- Interrupting condition imposed on a circuit breaker connected with fault current limiter2003
- Reduction effect of semiconductor type fault current limiter on interrupting duty of a circuit breaker2003
- Model of HTS three-phase saturated core fault current limiterIEEE Transactions on Applied Superconductivity, 2000
- Development of passive fault current limiter in parallel biasing modeIEEE Transactions on Magnetics, 1999
- Principle and characteristics of a fault current limiter with series compensationIEEE Transactions on Power Delivery, 1996