Audible noise analysis of 750‐kV AC transmission line in high‐altitude area under different weather
Open Access
- 11 April 2023
- journal article
- research article
- Published by Institution of Engineering and Technology (IET) in IET Generation, Transmission & Distribution
- Vol. 17 (11) , 2644-2654
Abstract
In order to build UHV AC transmission lines at high altitudes, it is necessary to analyze the audible noise (AN) characteristics of the existing EHV transmission lines at high‐altitude areas to guide the design. The typical test data of AN for 750‐kV single‐circuit transmission lines measured at the Guanting long‐term observation station, located at an altitude of 1854 m, were collected. Two methods of sorting the test data of AN and extracting valid data were given. Then the levels of AN under different weather conditions were analyzed, which showed that AN was raised with the increase of instantaneous rainfall and snowfall. Typical frequency spectrums of AN under different weather were also obtained, the pure tone at 100 Hz was more prominent under rainy and snowy weather, and the pure‐tone oscillation attenuated at different positions. The statistical results and the calculated difference of AN over 5.5 h with continuous rainfall were obtained. For the 750‐kV transmission line in the quiet plateau areas, the calculated difference between AN during rainy days and fair weather can be taken as 25 dB, and the calculated value of the altitude correction coefficient of 2.85 dB/1000 m is better consistent with the measured value.Keywords
All Related Versions
This publication has 17 references indexed in Scilit:
- Effect of Altitude on the Audible Noise Level of AC Power linesEnergies, 2017
- Audible Noise Performance of Conductor Bundles Based on Cage Test Results and Comparison with Long Term DataEnergies, 2017
- The Altitude Effect and Correction of Audible Noise for HVdc Transmission LinesIEEE Transactions on Power Delivery, 2016
- Analysis of positive DC corona inception voltage of stranded conductor at different altitudes2014
- AC Conductors' Corona-Loss Calculation and Analysis in Corona CageIEEE Transactions on Power Delivery, 2012
- Audible noise performance of 6-rail conductors on a 765-kV double circuit test lineIEEE Transactions on Power Delivery, 1997
- Comparison of several methods for calculating power line electromagnetic interference levels and calibration with long term dataIEEE Transactions on Power Delivery, 1992
- Measurement and Analysis of Audible Noise From Operating 765 kV Transmission LinesIEEE Power Engineering Review, 1981
- Long Term Audible Noise and Radio Noise Performance of American Electric Power's Operating 765 KV LinesIEEE Transactions on Power Apparatus and Systems, 1979
- Predetermination of Corona Losses Under Rain: Influence of Rain Intensity and Utilization of a Universal ChartIEEE Transactions on Power Apparatus and Systems, 1970