Computing Criticality of Lines in Power Systems
- 1 May 2007
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- No. 02714302,p. 65-68
Abstract
The authors propose a computationally efficient method based on nonlinear optimization to identify critical lines, failure of which can cause severe blackouts. The method computes criticality measure for all lines at a time, as opposed to detecting a single vulnerability, providing a global view of the system. This information on criticality of lines can be used to identify multiple contingencies by selectively exploring multiple combinations of broken lines. The effectiveness of our method is demonstrated on the IEEE 30 and 118 bus systems, where we can quickly detect the most critical lines and identify severe multiple contingencies.Keywords
This publication has 4 references indexed in Scilit:
- Power System Extreme Event Screening using Graph Partitioning2006
- Identification of severe multiple contingencies in electric power networks2005
- On the Solution of the Bilevel Programming Formulation of the Terrorist Threat ProblemIEEE Transactions on Power Systems, 2005
- Analysis of Electric Grid Security Under Terrorist ThreatIEEE Transactions on Power Systems, 2004