Determination of the power transmission line ageing failure probability due to the impact of forest fire
Authors:
Open Access
- 23 July 2018
- journal article
- research article
- Published by Institution of Engineering and Technology (IET) in IET Generation, Transmission & Distribution
- Vol. 12 (16) , 3812-3819
Abstract
With increased occurrences of a forest fire, the short‐term reliability of power transmission lines needs to be re‐evaluated considering the impact of forest fire on the ageing of transmission lines. How to include the impacts from a forest fire on line ageing in a comprehensive way becomes an important issue for the study of line failure probability. In this study, a method is proposed to evaluate the impact of forest fire on line ageing degree based on dynamic heat balance equation and Weibull distribution. The method will help maintenance staffs to assess the damage level of transmission lines. The method is tested by a contrast experiment and a case study with real meteorological data. Simulation results show that forest fire can greatly threaten the reliability of power transmission lines, while during this process flame characteristics, wind and load ratio could be the major factors that affect the line reliability. With the results obtained, this study also provides the system operator with valuable instructions on how to reduce the damages caused by fire to transmission lines.Keywords
Funding Information
- National Natural Science Foundation of China (51676054)
- Research Grants Council, University Grants Committee (T23‐701/14‐N)
This publication has 26 references indexed in Scilit:
- Study on the breakdown characteristics of the transmission line gap under forest fire conditionsInternational Transactions on Electrical Energy Systems, 2014
- Prospects for novel deformation processed Al/Ca composite conductors for overhead high voltage direct current (HVDC) power transmissionElectric Power Systems Research, 2013
- CRITICAL AGING SEGMENTS OF POWER TRANSMISSION LINEAmerican Journal of Engineering and Applied Sciences, 2013
- An analytical model based on radiative heating for the determination of safety distances for wildland firesFire Safety Journal, 2011
- Influence of the conductor temperature error on the overhead line ampacity monitoring systemsIET Generation, Transmission & Distribution, 2011
- Overhead lines insulation distance reduction due to stay wire's expansion from ground firesIET Generation, Transmission & Distribution, 2009
- Establishing safety distances for wildland firesFire Safety Journal, 2008
- A review of radiant heat flux models used in bushfire applicationsInternational Journal of Wildland Fire, 2003
- Firefighter Safety Zones: A Theoretical Model Based on Radiative HeatingInternational Journal of Wildland Fire, 1998
- Assesment of thermal deterioration of transmission line conductor by probabilistic methodIEEE Transactions on Power Delivery, 1998