Development of a Saturated Core Fault Current Limiter With Open Magnetic Cores and Magnesium Diboride Saturating Coils
Authors:
- 20 December 2016
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Applied Superconductivity
- Vol. 27 (4) , 1-7
Abstract
This paper describes the main characteristics and the performance of a saturated core type fault current limiter (FCL) rated 45 MVA (33 kV-800 A) to be provided by ASG Power Systems. The FCL, which has been submitted to preliminary laboratory testing, will be installed at a 275/33 kV substation in the U.K. and will reduce the fault current by 38%. The device is based on an open geometry of the magnetic cores which allows reduced size and the weight. Magnetic saturation of the cores is obtained by means of two magnesium diboride (MgB2) magnets. A numerical model of the FCL has been developed and validated and the interaction of the device with the power grid has been investigated. Details and results of the model are also discussed in the paper.Keywords
Funding Information
- OFGEM Low Carbon Network Fund, Tier 1 in the U.K
This publication has 15 references indexed in Scilit:
- Saturated iron-core superconductive fault current limiter developed at InnopowerAIP Conference Proceedings, 2014
- Dynamic core length in saturated core fault current limitersSuperconductor Science and Technology, 2013
- Coupled Electromagnetic-Thermal Model and Equivalent Circuit of a Magnetic Shield Type SFCLIEEE Transactions on Applied Superconductivity, 2013
- State of the art of superconducting fault current limiters and their application to the electric power systemPhysica C: Superconductivity and its Applications, 2013
- Analysis of electromagnetic forces in high voltage superconducting fault current limiters with saturated coreInternational Journal of Electrical Power & Energy Systems, 2012
- Development of a 220 kV/300 MVA superconductive fault current limiterSuperconductor Science and Technology, 2012
- A Modified Formulation of the Volume Integral Equations Method for 3-D MagnetostaticsIEEE Transactions on Magnetics, 2010
- DC Magnetization System for a 35 kV/90 MVA Superconducting Saturated Iron-Core Fault Current LimiterIEEE Transactions on Applied Superconductivity, 2009
- Magnetic Flux Density and Vector Potential of Uniform Polyhedral SourcesIEEE Transactions on Magnetics, 2007
- A Current Limiting Device Using Superconducting D.C. Bias Applications and ProspectsIEEE Transactions on Power Apparatus and Systems, 1982