Impact of inverter interfaced distributed generation on overcurrent protection in distribution systems
Authors:
- 1 September 2011
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- Vol. 2, 371-376
Abstract
The fault behavior of an inverter interfaced distributed generator (IIDG) is determined by its control, which is significantly different from a conventional generator. This paper examines in detail the key features of IIDG's fault behavior with respect to interference with distribution protection. As an example, the fault behavior of a commercially available photovoltaic converter is shown through a hardware-in-the-loop (HIL) simulation using real-time digital simulator (RTDS). A case study is then performed using the HIL setup to investigate the impact of IIDG on the recloser-fuse coordination in the fuse saving mode. The results illustrate that due to fault current limiting behavior of inverters, IIDG marginally impact primary and back-up protection in a distribution system. But with high penetration level, IIDGs may disturb the recloser-fuse coordination.Keywords