Energy Storage Systems (ESSs) are a promising solution for managing electrical grid congestion. However, in the European Union, regulations aimed at preventing electricity market interference restrict grid operators from the conventional use of ESSs. To overcome this restriction, Virtual Power Lines (VPLs) have been proposed in earlier research. VPLs are groups of ESSs operated such that their aggregated power is net zero at all time steps, thereby avoiding market interference. We formulate a MILP for the optimal siting and sizing of VPLs.We first show that optimal siting matters more for VPLs than for ESSs: randomized siting captures only 42.1% of the congestion reduction achievable with optimally sited VPLs, but captures 67.6% of that achievable with optimally sited ESSs. Next, we compare VPLs against conventional ESSs and show that VPLs have an effectiveness between 57.6% and 92.6% compared to ESSs of the same size. We also observe that the optimal siting of VPLs places an ESS at the slack node in 94.1% of cases, and validate their importance.These results give grid operators insight into how to use a practical, regulation compliant tool for relieving congestion, while also exposing the price of the policy that makes such workarounds necessary.