Three-Dimensional FDTD Calculation of Lightning-Induced Voltages on a Multiphase Distribution Line With the Lightning Arresters and an Overhead Shielding Wire
Authors:
- 1 February 2014
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Electromagnetic Compatibility
- Vol. 56 (1) , 159-167
Abstract
To suppress the lightning-induced voltages on a distribution line, lightning arresters and/or overhead shielding wire can be installed, and the effectiveness of these countermeasures are usually studied by simulations. Traditionally, field-to-transmission line coupling techniques based on the distributed-parameter circuit theory are used for the calculation of the lightning-induced voltages. Recently, the finite-difference time-domain (FDTD) method that directly and numerically solves Maxwell's equations was applied to the calculation of the lightning-induced voltages. Compared with the conventional methods, the FDTD-based calculation is advantageous in terms of the modeling of inhomogeneous ground parameters, 3-D structures, and grounding systems. But, in the previous works, the distribution line was simulated simply by a single-phase line. Moreover, the representation of lightning arresters in the FDTD method was not yet established. This paper proposes a technique to incorporate the lightning arresters in the FDTD-based lightning overvoltage calculations. In this technique, the voltage-current relationships of the lightning arresters are represented by piecewise linear curves, which can be obtained directly from the data sheets or measured results. For validation purpose, the lightning-induced voltages on a three-phase distribution line equipped with the lightning arresters and a multipoint-grounded overhead shielding wire are calculated by the proposed method, and the results are compared with those obtained by the conventional method and a very good agreement is found.Keywords
This publication has 48 references indexed in Scilit:
- Using a Two-Step Finite-Difference Time-Domain Method to Analyze Lightning-Induced Voltages on Transmission LinesIEEE Transactions on Electromagnetic Compatibility, 2011
- FDTD calculation of lightning-induced voltages on an overhead two-wire distribution line2010
- Evaluation of Lightning-Induced Voltages Over a Lossy Ground by the Hybrid Electromagnetic ModelIEEE Transactions on Electromagnetic Compatibility, 2009
- Applications of Time-Domain Numerical Electromagnetic Code to Lightning Surge AnalysisIEEE Transactions on Electromagnetic Compatibility, 2007
- Voltages Induced on an Overhead Wire by Lightning Strikes to a Nearby Tall Grounded ObjectIEEE Transactions on Electromagnetic Compatibility, 2006
- HEM: A Model for Simulation of Lightning-Related Engineering ProblemsIEEE Transactions on Power Delivery, 2005
- Numerical electromagnetic analysis of lightning-induced voltage over ground of finite conductivityIEEE Transactions on Electromagnetic Compatibility, 2003
- Advanced observations of lightning induced voltage on power distribution lines. IIIEEE Transactions on Power Delivery, 1989
- An integro-differential equation technique for the time-domain analysis of thin wire structures. I. The numerical methodJournal of Computational Physics, 1973
- Numerical solution of 2-dimensional scattering problems using a transmission-line matrixProceedings of the Institution of Electrical Engineers, 1971