Modified droop control scheme for load sharing amongst inverters in a micro grid
Authors:
- Urvi N. PatelUPUrvi N. Patel
- Dipakkumar GondaliaDGDipakkumar Gondalia
- Hiren H. PatelHPHiren H. Patel
- 25 June 2015
- journal article
- Published by Techno-Press in Advances in Energy Research
- Vol. 3 (2) , 81-95
Abstract
Modified droop control scheme for load sharing amongst inverters in a micro grid droop control;virtual impedance loop;arctan function;reactive power sharing; Microgrid, which can be considered as an integration of various dispersed resources (DRs), is characterized by number of DRs interfaced through the power electronics converters. The microgrid comprising these DRs is often operated in an islanded mode. To minimize the cost, reduce complexity and increase reliability, it is preferred to avoid any communication channel between them. Consequently, the droop control method is traditionally adopted to distribute active and reactive power among the DRs operating in parallel. However, the accuracy of distribution of active and reactive power among the DRs controlled by the conventional droop control approach is highly dependent on the value of line impedance, R/X i.e., resistance to reactance ratio of the line, voltage setting of inverters etc. The limitations of the conventional droop control approach are demonstrated and a modified droop control approach to reduce the effect of impedance mis-match and improve the time response is proposed. The error in reactive power sharing is minimized by inserting virtual impedance in line with the inverters to remove the mis-match in impedance. The improved time response is achieved by modifying the real-power frequency droop using arctan function. Simulations results are presented to validate the effectiveness of the control approach.Keywords
This publication has 9 references indexed in Scilit:
- Arctan Power–Frequency Droop for Improved Microgrid StabilityIEEE Transactions on Power Electronics, 2012
- Virtual Impedance Loop for Droop-Controlled Single-Phase Parallel Inverters Using a Second-Order General-Integrator SchemeIEEE Transactions on Power Electronics, 2010
- An Accurate Power Control Strategy for Power-Electronics-Interfaced Distributed Generation Units Operating in a Low-Voltage Multibus MicrogridIEEE Transactions on Power Electronics, 2009
- Decentralized Control for Parallel Operation of Distributed Generation Inverters Using Resistive Output ImpedanceIEEE Transactions on Industrial Electronics, 2007
- Wireless-Control Strategy for Parallel Operation of Distributed-Generation InvertersIEEE Transactions on Industrial Electronics, 2006
- Output Impedance Design of Parallel-Connected UPS Inverters With Wireless Load-Sharing ControlIEEE Transactions on Industrial Electronics, 2005
- 3C strategy for inverters in parallel operation achieving an equal current distributionIEEE Transactions on Industrial Electronics, 2000
- Control of parallel inverters in distributed AC power systems with consideration of line impedance effectIEEE Transactions on Industry Applications, 2000
- Control of parallel connected inverters in standalone AC supply systemsIEEE Transactions on Industry Applications, 1993