Investigation of Cellulose Insulation Aging in Transformers Retrofilled With Ester Fluids at Different Service Years
- 5 March 2024
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Dielectrics and Electrical Insulation
- Vol. 31 (4) , 2151-2160
Abstract
Retro-filling transformers with ester fluids have been increasingly practiced. Transformers may be retrofilled at different service years. In this paper, the ageing behaviour of the cellulose insulation of transformers retrofilled at different service years (with different conditions of paper insulation) are studied. Since the temperature may rise after the retrofill due to the high viscosity of the ester liquids, a temperature increase of 10 °C and 20 °C in cellulose-liquid insulation systems after retrofill is considered. The degree of polymerization (DP) of the cellulose insulation and the moisture in both cellulose and liquid insulation are measured before and after retrofilling. The measurements are used for modelling the remaining useful life of the cellulose-liquid insulation system. The process of insulation systems reaching the impregnation equilibrium after retrofilling is investigated through the fire and flash point measurements of the liquid insulation and frequency domain spectroscopy (FDS) measurements of the cellulose-liquid insulation system.Keywords
This publication has 22 references indexed in Scilit:
- Assessment of Flash and Fire point Measurements in Synthetic Ester under Retrofilling Scenarios2022
- Hot spot temperature for 154 kV transformer filled with mineral oil and natural ester fluidIEEE Transactions on Dielectrics and Electrical Insulation, 2012
- A survey of aging characteristics of cellulose insulation in natural ester and mineral oilIEEE Electrical Insulation Magazine, 2011
- Study on aging characteristics of mineral oil/natural ester mixtures-paper insulation2011
- Aging of pressboard in different insulating liquids2011
- Understanding the impacts of moisture and thermal ageing on transformer's insulation by dielectric response and molecular weight measurementsIEEE Transactions on Dielectrics and Electrical Insulation, 2008
- Aging of paper insulation retrofilled with natural ester dielectric fluid2004
- Retrofilling aging transformers with natural ester based dielectric coolant for safety and life extension2003
- Challenge of mixed insulating liquids for use in high-voltage transformers. II. Investigations of mixed liquid impregnated paper insulationIEEE Electrical Insulation Magazine, 2002