Root Cause Analysis of AC Overcurrent in July 2020 San Fernando Disturbance
- 2 July 2021
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Systems
- Vol. 36 (5) , 4892-4895
Abstract
On July 7 2020, approximately 1000 MW reduction in solar photovoltaic (PV) output was experienced by the bulk power system in Southern California after a three-phase fault. Disturbance analysis indicates that instantaneous AC current caused inverter tripping. The projection of the root cause of AC overcurrent from the NERC report is that inverter current control is not tight. This letter provides a quantitative analysis on ac overcurrent and addresses the following questions: (i) what type of current controls may lead to ac overcurrent and (ii) how controller parameters and grid strength may influence ac overcurrent. The letter provides frequency-domain analysis and time-domain simulation results of a grid-integrated inverter to illustrate the effect of control parameters and grid strength on ac overcurrent.Keywords
Funding Information
- U.S. Department of Energy Solar Energy Technology Office (DE-EE-0008771)
This publication has 3 references indexed in Scilit:
- Subcycle Overvoltage Dynamics in Solar PVsIEEE Transactions on Power Delivery, 2020
- Overview of Control and Grid Synchronization for Distributed Power Generation SystemsIEEE Transactions on Industrial Electronics, 2006
- Stationary frame current regulation of PWM inverters with zero steady-state errorIEEE Transactions on Power Electronics, 2003