Abstract
We describe the use of the constant injection tracer gas technique to study turbulent flow in a rectangular duct. A comparison between tracer gas measurements and measurements made using a hot-wire anemometer and a pitot tube is presented. Tracer gas concentration, air velocity and pressure distribution were measured at various distances from the duct wall and inlet. The Reynolds number based on the hydraulic diameter and the bulk velocity was varied between 7.5 x 10 3 and 18.6 x 103. An empirical equation for the entrance length required for fully developed turbulent flow was obtained and this was compared with experimental results.Keywords
This publication has 6 references indexed in Scilit:
- Interzone air movement and its effect on condensation in housesApplied Energy, 1989
- Measurements of turbulent flow in a duct with repeated ribs applied to two opposite wallsJournal of the Chinese Institute of Engineers, 1988
- Measurement of air flow between the floors of houses using a portable SF6 systemEnergy and Buildings, 1988
- Reynolds Number Dependence of Skin Friction and Other Bulk Flow Variables in Two-Dimensional Rectangular Duct FlowJournal of Fluids Engineering, 1978
- Measurements in Fully Developed Turbulent Channel FlowJournal of Fluids Engineering, 1975
- A Comparison of Predicted and Measured Friction Factors for Turbulent Flow Through Rectangular DuctsJournal of Heat Transfer, 1962