Post-Fault Active Power Control of DFIGs for Improving Multi-Swing Transient Stability-Part II: Strategy Application
- 27 May 2022
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- Vol. 41, 1263-1266
Abstract
As the second part of this two-part paper, this paper proposes a post-fault active power control of doubly-fed induction generators (DFIGs) to improve the multi-swing transient stability (MSTS). Based on the theoretical foundation in the first part., a control principle is presented with the theoretical analysis., where the control period is divided into three phases., and the corresponding control method in each phase is proposed. Then., a practical control strategy is proposed to apply the control principle in the actual engineering operation. Case studies on the modified New England 10-machine 39-bus system show that the proposed control strategy can effectively improve the MSTS when compared with typical control strategies.Keywords
This publication has 13 references indexed in Scilit:
- Transient Stability Enhancement of Power Grid With Integrated Wide Area Control of Wind Farms and Synchronous GeneratorsIEEE Transactions on Power Systems, 2017
- Co-Ordinated Multiloop Switching Control of DFIG for Resilience Enhancement of Wind Power Penetrated Power SystemsIEEE Transactions on Sustainable Energy, 2016
- Coordinated fault‐ride‐through strategy for doubly‐fed induction generators with enhanced reactive and active power supportIET Renewable Power Generation, 2016
- Active Power Control of DFIG-Based Wind Farm for Improvement of Transient Stability of Power SystemsIEEE Transactions on Power Systems, 2016
- Transient stability of power system integrated with doubly fed induction generator wind farmsIET Renewable Power Generation, 2015
- A Decomposition-Based Practical Approach to Transient Stability-Constrained Unit CommitmentIEEE Transactions on Power Systems, 2014
- Transient tripping control of large-scale wind power integration system2014
- Modeling and Validation of DFIG 3-MW Wind Turbine Using Field Test Data of Balanced and Unbalanced Voltage SagsIEEE Transactions on Sustainable Energy, 2011
- Integration of large-scale wind farm projects including system reliability analysisIET Renewable Power Generation, 2011
- A new tool for dynamic security assessment of power systemsControl Engineering Practice, 1998