Experimental Study on the Acceleration Amplification Ratio of Cable Terminations for Electric Power Facilities
Open Access
Abstract
Among national infrastructure facilities, electric power facilities are very important sites that must maintain their functions properly even during a natural disaster or during social crises. Therefore, seismic design is required when necessary for major electric power facilities that have a significant impact when damaged in the event of an earthquake. In electric power facilities, bushings are generally installed in devices or structures. Therefore, ground acceleration can be amplified through devices, such as transformers, or sub-structures. Among various electric power facilities, cable terminations are representative cantilever-type substation facilities consisting of a bushing, a sub-structure, and support insulators. The bushings of cable terminations are generally made of porcelain or fiber-reinforced plastic (FRP) materials, and they may have different dynamic characteristics. This study attempted to estimate the acceleration amplification ratio in the main positions of cable terminations considering the materials of bushings. For two cable terminations with different specifications and bushing materials, three-axis shake table tests were conducted in accordance with IEEE 693, which includes a seismic performance evaluation method for a power substation facility. The acceleration amplification ratios at the top of the bushing, mass center, and top of the support structure were estimated using the acceleration responses of each cable termination. They were then compared with the acceleration amplification factors presented in design standards. Consequently, the acceleration amplification ratio of cable termination with an FRP bushing was lower than that of the cable termination with a porcelain bushing.Keywords
Funding Information
- Korea Institute of Energy Technology Evaluation and Planning (20224B10200080)
This publication has 12 references indexed in Scilit:
- Evaluation of MCC seismic response according to the frequency contents through the shake table testNuclear Engineering and Technology, 2021
- Study on Seismic Performance of Porcelain Pillar Electrical Equipment Based on Nonlinear Dynamic TheoryAdvances in Civil Engineering, 2021
- Response of a 230 kV outdoor termination according to the frequency characteristics of input seismic wavesEnergy Reports, 2020
- An adaptive‐passive retuning device for a pendulum tuned mass damper considering mass uncertainty and optimum frequencyStructural Control and Health Monitoring, 2019
- Seismic Performance Evaluation of 500 kV EBATransactions of the Korean Society for Noise and Vibration Engineering, 2015
- Performance of industrial facilities in the Chilean earthquake of 27 February 2010The Structural Design of Tall and Special Buildings, 2010
- Experimental Seismic Response of High‐Voltage Transformer‐Bushing SystemsEarthquake Spectra, 2005
- Rocking stiffness of mounting arrangements in electrical cabinets and control panelsNuclear Engineering and Design, 2003
- Chapter A. The Loma Prieta, California, Earthquake of October 17, 1989 - Lifelines1998
- Dynamic amplification of electrical cabinets. [1--100Hz]1988