Abstract
Summary: This paper reports the results of an experimental study on two types of intumescent coating exposed to the ISO834 standard fire and three nonstandard fire curves. The nonstandard fires were all less severe than the standard fire. A total of 72 intumescent coating protected steel specimens were tested. The expanded thickness of intumescent char was measured, and the pore feature was observed. Constant thermal conductivity for each specimen was calculated based on the measured steel plate temperature. Thermogravimetric analysis (TGA) test was carried out, and the results show that more gas is trapped within the coating due to better matching of thermal behaviour between gas evolution and polymer viscosity as the rate of heating increases. The constant effective thermal conductivities for the intumescent coating under the nonstandard fires were 65% (type‐W) and 35% (type‐S) higher than that under the standard fire, which resulted in an overestimation of the coating failure time up to 15 and 11 minutes, respectively. Therefore, it is sometimes insecure to use results from standard fire tests guiding the design of coating thickness for steel elements under nonstandard fire conditions.