Abstract
The paper deals with the evaluation of the indirect-lightning performance of overhead distribution networks. The novelty of this contribution is that it takes into account the inherent complexity of distribution networks. These networks are indeed characterized by a plurality of lines (main feeder and laterals) and also by the presence of typical power components (e.g., transformers and surge arresters); they consequently differ considerably from the straight line configuration generally adopted in this type of studies. To accomplish such an evaluation we have extended the general procedure already presented in a previous paper based on the use of the LIOV code along with the Monte Carlo method. The extended procedure combines the advantage of the LIOV-EMTP computer code-that allows the calculation of lightning-induced voltages in complex distribution networks-with a heuristic technique specifically developed and integrated in the Monte Carlo routine in order to reduce the computational effort. The application of the proposed procedure to a set of distribution overhead networks characterized by different topologies, but all of the same length, shows that, in general, the usual single straight-line approach may result into a misestimation of the indirect-lightning performance. The paper also analyzes and discusses the influence of both the line terminations, and the position of the line poles.Keywords
This publication has 9 references indexed in Scilit:
- Lightning-Induced Overvoltages Transferred Through Distribution Power TransformersIEEE Transactions on Power Delivery, 2008
- An Improved Procedure for the Assessment of Overhead Line Indirect Lightning Performance and Its Comparison with the IEEE Std. 1410 MethodIEEE Transactions on Power Delivery, 2006
- Lightning-induced voltages on complex distribution systems: models, advanced software tools and experimental validationJournal of Electrostatics, 2004
- Mitigation of Lightning-Induced Overvoltages in Medium Voltage Distribution Lines by Means of Periodical Grounding of Shielding Wires and of Surge Arresters: Modeling and Experimental ValidationIEEE Transactions on Power Delivery, 2004
- Influence of a lossy ground on lightning-induced voltages on overhead linesIEEE Transactions on Electromagnetic Compatibility, 1996
- Modeling guidelines for fast front transientsIEEE Transactions on Power Delivery, 1996
- Lightning-induced voltage on an overhead wire dependent on ground conductivityIEEE Transactions on Power Delivery, 1994
- Radial distribution test feedersIEEE Transactions on Power Systems, 1991
- Transient Response of Multiconductor Transmission Lines Excited by a Nonuniform Electromagnetic FieldIEEE Transactions on Electromagnetic Compatibility, 1980