Influence of voltage measurement accuracy on the impedance estimation by a power conditioning system
Authors:
- 18 August 2020
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 44-49
Abstract
A kW-class residential photovoltaic power generation system (hereinafter referred to as PV) is connected to a low-voltage distribution system, and when they are mass-connected, a problem of voltage rise due to reverse power flow in the distribution system occurs. The power conditioning system (hereinafter referred to as PCS) has a function as a countermeasure on the PV side. Since this function includes output power suppression, inequality arises that the PV system connected to the terminal of the distribution lines tends to lose power generation opportunities more. One way to solve this problem is the leading reactive power control, where each PV system suppresses only the voltage rise caused by own active power output. However, in order to do this, information on the grid-side impedance (resistive component R and reactive component X) from the PCS is necessary, which is difficult to be obtained by residential customers in general. Therefore, the impedance estimation method using only the information which can be acquired by the PCS itself was investigated. As a result of tests, it was found that the estimated value by the PCS data has a higher error than the value estimated by another data acquired by a high-precision power meter. Since variation of the terminal voltage is slight even if active power and reactive power change drastically, the influence of voltage measurement accuracy on the impedance estimation accuracy was evaluated.Keywords