Abstract
The article presents the results of a study of the impact of capacitive currents, transient resistances, and the distance of double short circuits on the excessive opera- tion and non-operation of zero-sequence current protections and overcurrent protections of power inputs of power center busbars of 20 kV distribution electrical networks. It is shown that zero-sequence current protections fail to operate success- fully at capacitive currents of 300 A or more and at transient resistances over 30 Ω. Replacing the zero-sequence current protections with the current protections that use minimum-max- imum phase current selectors ensures satisfactory protection operation with capacitive currents up to 525 A and transient resistances up to 40 Ω.