Testing and modelling of voltage transformer for high order harmonic measurement
Authors:
- 1 July 2011
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 229-233
Abstract
Harmonics have become an important concern in today's power system network. Conventional Inductive Voltage Transformers (IVT) are used as the essential instrument for harmonic measurement. However, the frequency bandwidths of the IVTs are limited. As a result, they are not suitable for high order harmonic measurement. This paper thus presents the testing and modelling of the frequency response of a 33kV single phase IVT up to 5 kHz. The test system setup for testing the IVT frequency response is described. The frequency response of a 33kV single phase IVT is measured and analyzed. A model of the 33kV IVT is developed and validated by comparing the simulation with the experimental results. Good correlation between the two results is observed. The impact of burden on the frequency response of the 33kV IVT is also simulated and discussed.Keywords
This publication has 6 references indexed in Scilit:
- Frequency Responses of MV voltage transformers in the range of 50 Hz to 10 kHz2010
- High frequency transformer computer modeling2007
- Power System Harmonics2003
- Method to measure CVT transfer functionIEEE Transactions on Power Delivery, 2002
- Voltage transformer frequency response. Measuring harmonics in Norwegian 300 kV and 132 kV power systems2002
- Potential Transformer Accuracy at 60HZ Voltages Above and Below Rating and at Frequencies Above 60 HZIEEE Transactions on Power Apparatus and Systems, 1981