Implementasi dan Pengujian Tahanan Isolasi pada Transformator Distribusi 200 kVA di PT. PLN (PERSERO) UP3 Pekanbaru
Open Access
- 1 June 2025
- journal article
- Published by Indra Institute in Jurnal Indragiri Penelitian Multidisiplin
- Vol. 5 (3) , 58-68
Abstract
Power transformers are high-voltage equipment that function to distribute electrical power, either from high voltage to low voltage or vice versa. However, if the insulation condition of the transformer experiences a decrease in quality, this can cause operational failure, even more serious damage that disrupts the electrical system as a whole. To prevent this, testing of the insulation resistance is required. One of the methods used to test this insulation condition is the polarization index method. This method is considered the most accurate and effective way to assess the feasibility of insulation resistance in transformers, especially those located in substations and distribution substations in Indonesia. This study was conducted by taking data from the location of PT. PLN (Persero) UP3 Pekanbaru. Through insulation resistance testing, the results of the measurement of the polarization index value were obtained. The data collected were then calculated and analyzed to obtain more optimal evaluation results. The results show that the polarization index value on the primary ground is at 1.25 and the secondary ground is 1.5. Both values are still in the good category, referring to the standard polarization index value which ranges from 1.25 to 2.0Keywords
This publication has 8 references indexed in Scilit:
- Analisis Hasil Pengujian Isolasi Transformator Daya 20 kV (Step-Up) di PT PLN (Persero) PLTD TeginenengElectrician : Jurnal Rekayasa dan Teknologi Elektro, 2025
- Temperature Monitoring System for 3 Phase Electric Arc Furnace (EAF) Transformer CoolingJambura Journal of Electrical and Electronics Engineering, 2024
- PEMANFAATAN STATISTICAL PACKAGE FOR THE SOCIAL SCIENCES (SPSS) UNTUK ANALISIS DATA STATISTIKJurnal Karya Abdi, 2024
- Analisis Susut Daya Dan Energi Pada Jaringan Distribusi Di Gardu Induk Kendari New Penyulang Brimob Menggunakan Software ETAP 19.0.1. Pada Waktu Beban PuncakJurnal Fokus Elektroda : Energi Listrik, Telekomunikasi, Komputer, Elektronika dan Kendali), 2023
- INFORMATION SYSTEMS OF OFFICIAL TRIPS AT GENERAL ELECTION COMMISSION OFFICE (KPU)) INDRAGIRI HILIR REGENCYJurnal Teknologi Informasi dan Pendidikan, 2021
- PENINGKATAN KETERAMPILAN PROSES SAINS SISWA MELALUI PENDEKATAN INKUIRI TERBIMBINGJurnal Penelitian dan Pembelajaran IPA, 2016
- The Technological Pedagogical Content Knowledge Framework2013
- Improvement of nursing students' critical thinking skills through problem‐based learning in the People's Republic of China: A quasi‐experimental studyNursing & Health Sciences, 2008