Fault detection and location in medium‐voltage DC microgrids using travelling‐wave reflections
Authors:
Open Access
- 21 February 2020
- journal article
- research article
- Published by Institution of Engineering and Technology (IET) in IET Renewable Power Generation
- Vol. 14 (4) , 571-579
Abstract
Fast dc fault detection method is required in medium‐voltage dc (MVDC) microgrids to avoid severe damage to the interfacing converters. Ensuring selectivity and sensitivity of the protection system within a few milliseconds is a major challenge. This study proposes a new technique based on fault launched travelling‐waves (TWs) to detect, classify, and locate different dc fault types in MVDC microgrids. Unlike the existing TW‐based protection and fault location methods, the proposed technique utilises the frequency of TW reflections, rather than their arrival time. Moreover, the fault initiated voltage TW is contained within the faulted line by adding smoothing inductors on line terminals, which (i) prevents relays on adjacent lines from detecting the TW and (ii) results in higher reflected TW magnitudes. Therefore, the proposed method's selectivity and sensitivity are enhanced compared to existing methods. Other salient features of the proposed scheme include a moderate sampling frequency of 2 MHz, detection speed of 128 μs, fault location accuracy of ±25 m, no communication requirement, and independence from system configuration. The proposed scheme's performance has been assessed using a ±2.5 kV TN‐S grounded MVDC microgrid under various conditions. The fault location accuracy of the proposed technique is compared to the conventional single‐terminal TW‐based method.Keywords
This publication has 28 references indexed in Scilit:
- Protection of Smart DC Microgrid With Ring Configuration Using Parameter Estimation ApproachIEEE Transactions on Smart Grid, 2017
- Microgrid ProtectionProceedings of the IEEE, 2017
- Centralized Protection Strategy for Medium Voltage DC MicrogridsIEEE Transactions on Power Delivery, 2016
- Validation of Fast and Selective Protection Scheme for an LVDC Distribution NetworkIEEE Transactions on Power Delivery, 2016
- A Non-unit Protection Scheme for DC Microgrid Based on Local MeasurementsIEEE Transactions on Power Delivery, 2016
- Hybrid Passive-Overcurrent Relay for Detection of Faults in Low-Voltage DC GridsIEEE Transactions on Smart Grid, 2015
- Multi‐Terminal Direct‐Current Grids2014
- An Advanced Protection Scheme for Enabling an LVDC Last Mile Distribution NetworkIEEE Transactions on Smart Grid, 2014
- Contribution of Fault Current Sources in Multiterminal HVDC Cable NetworksIEEE Transactions on Power Delivery, 2013