Proportional-integral-derivative λ-tuning for integrating processes with deadtime
Authors:
- 5 March 2010
- journal article
- Published by Institution of Engineering and Technology (IET) in IET Control Theory & Applications
- Vol. 4 (3) , 425-436
Abstract
Over the past 15 years, a number of model-based proportional-integral-derivative (PID) tuning methods have been developed for systems that can be described as integrating-with-deadtime. This was motivated by the observation that the initial open-loop response of lag-dominant processes, such as tray temperature in high-purity distillation columns, resembles that of a delayed ramp variable. This study compares the behaviour of several PID λ-tuning rules with the Skogestad internal model control (or SIMC) proportional-integral (PI) controller on simulated integrator-plus-deadtime and lag-dominant first-order plants. Guidelines are provided for selecting the most appropriate tuning method for a given application based on the primary function of the feedback loop (servo against regulatory) as well as the relative importance of control effort and robustness. In contrast, the PID version of the Tyreus–Luyben controller, a popular strategy for this class of models, was found to yield excellent setpoint following but sluggish rejection of unmeasured disturbances acting at the plant input.Keywords
This publication has 5 references indexed in Scilit:
- A Comparison of PID Controller Tuning MethodsThe Canadian Journal of Chemical Engineering, 2005
- Comparison of PI Controller Tuning MethodsIndustrial & Engineering Chemistry Research, 2005
- PI/PID Controller Design Based on Direct Synthesis and Disturbance RejectionIndustrial & Engineering Chemistry Research, 2002
- Effect of Derivative Algorithm and Tuning Selection on the PID Control of Dead-Time ProcessesIndustrial & Engineering Chemistry Research, 2001
- Internal model control: PID controller designIndustrial & Engineering Chemistry Process Design and Development, 1986