Very fast transients in GIS
Authors:
- K. FeserKFK. Feser
- W.R. PfaffWPW.R. Pfaff
- 1 January 1989
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 4 (1) , 223-233
Abstract
Different types of very fast transients (VFTs) are classified and their characteristic parameters are summarized based on measurements in a 800 kV SF/sub 6/ gas-insulated pilot installation and 420 kV GIS (gas-insulated switchgear) in service. The electromagnetic field between the enclosure and earth results in a transient enclosure voltage of up to some 10 kV and at the same time in a radiated electromagnetic field from the enclosure with amplitude of some 10 kV/m. The electromagnetic wave guided by the overhead line results in an overvoltage with a multifrequent oscillation of some 10 to 100 kHz, depending on the parameters of the overhead line and the adjacent equipment, e.g. the transformer. The transient enclosure voltage and measures to reduce it are analyzed.Keywords
This publication has 5 references indexed in Scilit:
- Distortion-free measurement of high impulse voltagesIEEE Transactions on Power Delivery, 1988
- Transient Ground Potential Rise in Gas-Insulated Substations - Problem Identification and MitigationIEEE Transactions on Power Apparatus and Systems, 1982
- Transient Ground Potential Rise in Gas Insulated Substations - Assessment of Shock HazardIEEE Transactions on Power Apparatus and Systems, 1982
- Transient Ground Potential Rise in Gas Insulated Substations - Experimental StudiesIEEE Transactions on Power Apparatus and Systems, 1982
- A High-Impedance, Nanosecond Rise Time Probe for Measuring High-Voltage ImpulsesIEEE Transactions on Power Apparatus and Systems, 1968