Fast DC fault location and isolation strategy for the flexible multi‐terminal DC system
Authors:
Open Access
- 31 August 2018
- journal article
- research article
- Published by Institution of Engineering and Technology (IET) in The Journal of Engineering
- Vol. 2018 (15) , 908-912
Abstract
Voltage source converters (VSCs) are highly vulnerable to DC fault current. Protection methods which can quickly locate and isolate DC faults are necessities in VSC‐based multi‐terminal DC (VSC‐MTDC) systems for its safe and reliable operation. In this paper, a fast and collaborative DC fault location and isolation strategy are proposed. In this strategy, hybrid DC circuit breakers (HDCCBs) are used as the main protection device. The operation control of HDCCB is redesigned and cooperates with fault location results to achieve fast fault isolation. For the fault location method, a fast d i /d t criterion is used for fault pretreatment, the transient‐voltage energy difference criterion is used to make sure its selectivity. The overall protection strategy is demonstrated in a four‐terminal VSC‐MTDC system using PSCAD/EMTDC platform. The performances of the typical DC circuit breaker‐based strategy and the proposed strategy were compared. Numerous simulation results under various conditions proved its flexibility and validity.Keywords
This publication has 6 references indexed in Scilit:
- Multi‐terminal medium voltage DC grids fault location and isolationIET Generation, Transmission & Distribution, 2016
- Dc fault protection of multi-terminal VSC-HVDC system with hybrid dc circuit breaker2016
- Assembly HVDC Breaker for HVDC Grids With Modular Multilevel ConvertersIEEE Transactions on Power Electronics, 2016
- Selective Wave-Front Based Protection Algorithm for MTDC Systems2016
- Protection issue discussion of DC network development: circuit breaker or fault-tolerant converter2012
- HVDC Circuit Breakers: A Review Identifying Future Research NeedsIEEE Transactions on Power Delivery, 2011