Distance Protection of AC Grid With HVDC-Connected Offshore Wind Generators
- 18 July 2013
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 29 (2) , 493-501
Abstract
When a transmission line close to points of common coupling (PCCs) experiences a short-circuit (SC) fault, the fast reactive power control of voltage-source converter-HVDC (VSC-HVDC) is likely to affect the protective relay operation of transmission lines. To study the performance of distance relays on an ac grid with an offshore wind HVDC network, this paper presents an apparent impedance calculation method, which utilizes the bus impedance matrix (Zbus) to calculate the impedances viewed by distance relays during a three-phase SC fault. The proposed method is used to identify the potential miscoordinated Zone 2 relays in the proposed combined ac/dc system. The analysis is verified by software simulation results. It is shown that the proposed method results in accurate impedances viewed by distance relays. It also identifies the protective device settings on the ac grid that need to be adjusted due to HVDC control of offshore wind generators.Keywords
This publication has 9 references indexed in Scilit:
- Tripping of wind turbines during a system fault2008
- Grid Integration of Large DFIG-Based Wind Farms Using VSC TransmissionIEEE Transactions on Power Systems, 2007
- Adaptive Distance Relay Setting for Lines Connecting Wind FarmsIEEE Transactions on Energy Conversion, 2007
- Performance Evaluation of a Distance Relay as Applied to a Transmission System With UPFCIEEE Transactions on Power Delivery, 2006
- Performance of Distance Relays on Shunt—FACTS Compensated Transmission LinesIEEE Transactions on Power Delivery, 2005
- A New Approach for Calculating Zone-2 Setting of Distance Relays and Its Use in an Adaptive Protection SystemIEEE Transactions on Power Delivery, 2004
- Optimal acquisition and aggregation of offshore wind power by multiterminal voltage-source HVDCIEEE Transactions on Power Delivery, 2003
- Adaptive relay setting for flexible AC transmission systems (FACTS)IEEE Transactions on Power Delivery, 2000
- Generalized Method of Analysis of Simultaneous Faults in Electric Power SystemIEEE Transactions on Power Apparatus and Systems, 1982