Transient Stability Analysis of Direct Drive Wind Turbine in DC-Link Voltage Control Timescale during Grid Fault
Open Access
Abstract
Transient stability during grid fault is experienced differently in modern power systems, especially in wind-turbine-dominated power systems. In this paper, transient behavior and stability issues of a direct drive wind turbine during fault recovery in DC-link voltage control timescale are studied. First, the motion equation model that depicts the phase and amplitude dynamics of internal voltage driven by unbalanced active and reactive power is developed to physically depict transient characteristics of the direct drive wind turbine itself. Considering transient switch control induced by active power climbing, the two-stage model is employed. Based on the motion equation model, transient behavior during fault recovery in a single machine infinite bus system is studied, and the analysis is also divided into two stages: during and after active power climbing. During active power climbing, a novel approximate analytical expression is proposed to clearly reveal the frequency dynamics of the direct drive wind turbine, which is identified as approximate monotonicity at excitation of active power climbing. After active power climbing, large-signal oscillation behavior is concerned. A novel analysis idea combining time-frequency analysis based on Hilbert transform and high order modes is employed to investigate and reveal the nonlinear oscillation, which is characterized by time-varying oscillation frequency and amplitude attenuation ratio. It is found that the nonlinear oscillation and even stability are related closely to the final point during active power climbing. With a large active power climbing rate, the nonlinear oscillation may lose stability. Simulated results based on MATLAB® are also presented to verify the theoretical analysis.Keywords
Funding Information
- National Natural Science Foundation of China (52107137)
This publication has 30 references indexed in Scilit:
- Small Signal Instability of PLL-Synchronized Type-4 Wind Turbines Connected to High-Impedance AC Grid During LVRTIEEE Transactions on Energy Conversion, 2016
- Voltage Dynamics of Current Control Time-Scale in a VSC-Connected Weak GridIEEE Transactions on Power Systems, 2015
- Analysis of D-Q Small-Signal Impedance of Grid-Tied InvertersIEEE Transactions on Power Electronics, 2015
- Impact of Short-Circuit Ratio and Phase-Locked-Loop Parameters on the Small-Signal Behavior of a VSC-HVDC ConverterIEEE Transactions on Power Delivery, 2014
- A review of grid code technical requirements for wind farmsIET Renewable Power Generation, 2009
- Nonlinear, Non-Stationary Analysis of Interarea Oscillations via Hilbert Spectral AnalysisIEEE Transactions on Power Systems, 2006
- Inclusion of Higher Order Terms for Small-Signal (Modal) Analysis: Committee Report—Task Force on Assessing the Need to Include Higher Order Terms for Small-Signal (Modal) AnalysisIEEE Transactions on Power Systems, 2005
- Characterization of nonlinear modal interaction using normal forms and Hilbert analysis2005
- Identification of Instantaneous Attributes of Torsional Shaft Signals Using the Hilbert TransformIEEE Transactions on Power Systems, 2004
- Investigation of modal interaction and its effects on control performance in stressed power systems using normal forms of vector fieldsIEEE Transactions on Power Systems, 1996