Neuro wavelet algortihm for detecting high impedance faults in extra high voltage transmission systems
- 1 May 2017
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 97-100
Abstract
High impedance faults are not easy to be measured and detected by convetional relay protection. This paper proposed simualtions studies for detection high impedance fault in extra high voltage transmission line (EVT). The fault simulations based on simplified 2 diodes model. Current signal from the measurement is processed using discrete wavelet transform type haar wavelet to obtain coefficient detail. The output of discrete wavelet transform will be used for pattern recognition based on an backpropagation neural networks algorithm. The fault is modified to distribution system for EVT. The Characteristics of the proposed scheme are analyzed by comprehensive studies and the result clearly explain that it can accurately detect high impedance fault in the EVT with varies condition.Keywords
This publication has 7 references indexed in Scilit:
- A New Protection Detection Technique for High Impedance Fault Using Neural Network2006
- High Impedance Fault Detection Based on Wavelet Transform and Statistical Pattern RecognitionIEEE Transactions on Power Delivery, 2005
- High-Impedance Fault Detection Using Discrete Wavelet Transform and Frequency Range and RMS ConversionIEEE Transactions on Power Delivery, 2005
- A novel technique for high impedance fault identificationIEEE Transactions on Power Delivery, 1998
- Fault location using waveletsIEEE Transactions on Power Delivery, 1998
- An introduction to neural networks1997
- An adaptive high and low impedance fault detection methodIEEE Transactions on Power Delivery, 1994