A study of the mechanism by which atmospheric aerosol particles are charged in the vicinity of a unipolar HVDC line and a numerical analysis that predicts the magnitude of the wind-driven current carried by particulates was conducted. The major elements of the study are the following: equations for the rate of charging of particles in strong electric fields and unipolar ion environments are developed and numerical solutions are presented; the electrical mobility of charged particles is determined; numerical solutions to the equations that govern the electric field and ion density in the vicinity of a unipolar line for wind speeds of 0, 5, and 10 m/sec in the absence of aerosols are presented; and a numerical analysis of the magnitude of charge transferred to the aerosol as it is advected past the HVDC line as a function of wind speed is carried out for three aerosol size distribution models and three fog models. The results for a 400 kV unipolar HVDC line giving off 2.3 ..mu..amp per m predicts that 3 to 5% of the corona current will be transferred to aerosols in clean rural air, 4 to 12% in moderately polluted air, and possibly as much as 45% inmore » highly polluted air; higher transfer rates are predicted for fogs. Downwind the space charge and resulting electric fields are one to two orders of magnitude greater than the fair-weather background values. « less