DC Arc Flash Studies for Solar Photovoltaic Systems: Challenges and Recommendations
Author:
- Kathryn KlementKKKathryn Klement
- 11 May 2015
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Industry Applications
- Vol. 51 (5) , 4239-4244
Abstract
A dc arc flash hazard exists in solar photovoltaic (PV) power systems, but there is no widely accepted methodology for characterizing the severity of the hazard. Calculation methods have been proposed, and most rely on the nameplate I-V characteristic of the PV modules at standard test conditions to determine the worst case incident energy. This paper proposes to consider other factors in performing a dc arc flash hazard analysis, including possible weather conditions and variations of PV module characteristics from the datasheet ratings. It is recommended to consider two conditions when determining the worst case incident energy from a PV system: 1) the failure of all protective devices to trip within 2 s due to insufficient current and 2) the array output power exceeding the nameplate rating due to technological and environmental factors.Keywords
This publication has 6 references indexed in Scilit:
- Arc Flash Calculations for a 1.3-MW Photovoltaic SystemIEEE Transactions on Industry Applications, 2014
- DC Electric Arc-Flash Hazard-Risk Evaluations for Photovoltaic SystemsIEEE Transactions on Power Delivery, 2013
- DC Arc flash calculations for solar farms2013
- Arc Flash Calculations for Exposures to DC SystemsIEEE Transactions on Industry Applications, 2010
- DC-Arc Models and Incident-Energy CalculationsIEEE Transactions on Industry Applications, 2010
- Empirical studies of cloud effects on UV radiation: A reviewReviews of Geophysics, 2005