Nisqually Earthquake Electric Utility Analysis

Authors:

Abstract
The performance of an urban electric utility distribution system was evaluated for the February 2001 Nisqually earthquake. The restoration rate of the lifeline following the event was determined; the distribution of outage durations was estimated; and correlations between lifeline damage and instrumental Modified Mercalli intensity, peak ground velocity, and peak ground acceleration values were ascertained using a GIS (geographical information systems) approach. Using a logit regression analysis, a fragility curve was developed for the lifeline in a manner similar to O'Rourke's formulation of water‐line performance (O'Rourke et. al. 2000). Extrapolation of the model to the Seattle Fault earthquake scenario was made to demonstrate its feasibility for prediction.