Abstract
Summary: Electric power system is one of essential lifeline systems for an urban community. An actual power plant building with typical coal‐fired power generation process is selected to be studied in this paper. The detrimental impacts on the seismic performance of the structural system induced by heavy coal bunkers and irregular bracing configurations are expected to be mitigated by using retrofit strategies. A total of three retrofit design schemes that employ the isolation and supplemental damping techniques are developed. The original design scheme of the actual thermal power plant building that adopts steel special concentrically braced frame as lateral‐force resisting system is used as benchmark for comparison purposes. Nonlinear response‐history analyses are performed, and the obtained seismic responses are compared. To better quantify the benefit of the considered retrofit strategies, seismic risk in terms of probabilities of exceeding designated damage states as well as the downtime are analyzed. For the studied thermal power plant building, the results show that the added damping system is more effective in seismic risk reduction than the isolation for heavy coal bunkers. Compared to the original structural system design, the use of supplemental damping system cut the downtime of the thermal power plant building at most 42%.Keywords
Funding Information
- China Scholarship Council
- Fundamental Research Funds for the Central Universities
- National Natural Science Foundation of China (51878426, U1710111)
This publication has 45 references indexed in Scilit:
- Performance of industrial buildings during the Emilia earthquakes in Northern Italy and recommendations for their strengtheningBulletin of Earthquake Engineering, 2013
- Mitigation of Seismic Risks to Soft-Storey Structures Using Toggle-Brace-Damper SystemsApplied Mechanics and Materials, 2012
- Performance of industrial facilities in the Chilean earthquake of 27 February 2010The Structural Design of Tall and Special Buildings, 2010
- Comparative energetic and exergetic performance analyses for coal-fired thermal power plants in TurkeyInternational Journal of Thermal Sciences, 2009
- Risk assessment and early warning systems for industrial facilities in seismic zonesReliability Engineering & System Safety, 2009
- Influence of passive supplemental damping systems on structural and nonstructural seismic fragilities of a steel buildingEngineering Structures, 2008
- Fragility assessment of building structural systems in Mid‐AmericaEarthquake Engineering & Structural Dynamics, 2007
- Reducing residual drift of buckling-restrained braced frames as a dual systemEngineering Structures, 2006
- Seismic demands on steel braced frame buildings with buckling-restrained bracesEngineering Structures, 2003
- Earthquake risk assessment of building structuresReliability Engineering & System Safety, 2001