Revisiting Chien‐Hrones‐Reswick Method for an Analytical Solution
- 15 January 2026
- journal article
- Published by Wiley in Advanced Control for Applications
- Vol. 8 (1)
Abstract
This study presents an analytical method for tuning PI controllers in first‐order with time delay (FOTD) systems, leveraging the Lambert W function. The Lambert W function enables exact pole placement, yielding direct analytical expressions for PI gains. The proposed approach identifies a critical condition that achieves a step response without overshoot and with minimum settling time, while also providing explicit tuning rules for systems where controlled overshoot is specified. The method demonstrates strong agreement with established empirical Chien‐Hrones‐Reswick tuning rules for both non‐overshooting and overshooting cases, bridging the gap between theoretical analysis and empirical results.Keywords
All Related Versions
This publication has 5 references indexed in Scilit:
- Comparison of PI controller performances for a Conical Tank process using different tuning methods2014
- PI control of first order time-delay systems via eigenvalue assignment2011
- Time-Delay Systems2010
- The future of PID controlControl Engineering Practice, 2001
- Optimum Settings for Automatic ControllersJournal of Dynamic Systems, Measurement, and Control, 1993