Power transformer monitoring using UHF sensors: site trials
Authors:
- G.P. ClearyGCG.P. Cleary
- C.J. BennochCBC.J. Bennoch
- J.S. PearsonJPJ.S. Pearson
- T. BreckenridgeTBT. Breckenridge
- 1 April 2002
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 145-149
Abstract
Sensors operating in the ultra-high frequency (UHF) band have been used to detect internal discharges during site testing of a 1000 MVA oil-filled transformer. The transformer was operated at voltages exceeding normal levels by up to 15%. Two discharge sources were detected at both sensors using UHF test equipment. Discharge signals are analyzed in phase-resolved form and time-of-flight measurements are used to provide further information regarding their origin. The results indicate that the UHF method could prove very effective for transformer testing and online PD monitoring.Keywords