Improved design of cover plates of power transformers for lower eddy current losses
Authors:
- Song-Yop HahnSHSong-Yop Hahn
- Sang-Young KimSKSang-Young Kim
- 1 January 1999
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Magnetics
- Vol. 35 (5) , 3529-3531
Abstract
Due to the heavy current passing through the steel cover plates of power transformers, some areas are subject to serious local overheating. This affects the safety and reliability of the expensive equipment and power delivery. In this paper, the improved design of cover plates is presented to reduce eddy current losses and to protect them from local overheating. For the accurate calculation of eddy current losses and power loss density distribution in the cover plates, the indirect BIEM (boundary integral equation method) is applied to the 3D open boundary problem caused by the heavy current of leads in a three-phase power transformer. The numerical results by the indirect BIEM are compared with experimental values.Keywords
This publication has 4 references indexed in Scilit:
- Electromagnetic force analysis of moving conducting slab by using 3D IBIEMIEEE Transactions on Magnetics, 1998
- Eddy current losses and hot-spot evaluationin coverplates of power transformersIEE Proceedings - Electric Power Applications, 1997
- Eddy current fields and overheating problems due to heavy current carrying conductorsIEEE Transactions on Magnetics, 1994
- Boundary integral equations of minimum order for the calculation of three-dimensional eddy current problemsIEEE Transactions on Magnetics, 1982