Abstract
This paper proposes a direct stator current vector control strategy of a doubly fed induction generator (DFIG) without phase-locked loop (PLL) during network unbalance. In the proposed control strategy, a virtual phase angle produced by the nominal frequency is used for coordinate transformations instead of the actual voltage one estimated by the PLL. Since the calculation of the commanded stator currents is based on the instantaneous power theory regardless of the generator parameters, it can greatly reduce the parameter dependence of the control system. Then, for a satisfactory grid synchronization, an improved synchronization method is proposed. It can smoothly produce the stator voltage with no overshoot voltage and no parameter dependence. During network unbalance, a reduced-order vector integrator is used to directly regulate the pulsating components without the complex calculations of the commanded current values and the sequential separations of the voltages and currents. Meanwhile, four alternative control targets can be achieved for the DFIG during network unbalance. Furthermore, the control performance, including the control system stability, the robustness against frequency disturbances and parameter deviations, and the rejection of voltage unbalance, are fully analyzed. Finally, the experimental results are given to validate the effectiveness of the proposed control strategy.Keywords
This publication has 25 references indexed in Scilit:
- An Efficient Implementation of Generalized Delayed Signal Cancellation PLLIEEE Transactions on Power Electronics, 2015
- Analysis of D-Q Small-Signal Impedance of Grid-Tied InvertersIEEE Transactions on Power Electronics, 2015
- Collaborative Control of DFIG System During Network Unbalance Using Reduced-Order Generalized IntegratorsIEEE Transactions on Energy Conversion, 2014
- Modularized Control Strategy and Performance Analysis of DFIG System Under Unbalanced and Harmonic Grid VoltageIEEE Transactions on Power Electronics, 2014
- A Three-Phase PLL Algorithm Based on Signal Reforming Under Distorted Grid ConditionsIEEE Transactions on Power Electronics, 2014
- Independent Operation of DFIG-Based WECS Using Resonant Feedback Compensators Under Unbalanced Grid Voltage ConditionsIEEE Transactions on Power Electronics, 2014
- dq-Frame Cascaded Delayed Signal Cancellation- Based PLL: Analysis, Design, and Comparison With Moving Average Filter-Based PLLIEEE Transactions on Power Electronics, 2014
- Coordinated Control of DFIG's RSC and GSC Under Generalized Unbalanced and Distorted Grid Voltage ConditionsIEEE Transactions on Industrial Electronics, 2012
- Operation of Wind-Turbine-Driven DFIG Systems Under Distorted Grid Voltage Conditions: Analysis and Experimental ValidationsIEEE Transactions on Power Electronics, 2011