Research and application of Wide-Band modeling method for flexible HVDC converter valve

Authors:

Abstract
Electromagnetic disturbance(EMD) of the flexible DC converter station is mainly caused by the periodic turn-on and turn-off of the power electronic switch. And it will affect the secondary equipment in the form of conduction. In order to make the simulation results of the MMC electromagnetic transient model more accurate at high frequencies, it is essential to develop models of the valve over a wide frequency range. In this paper, the impedance characteristics of each passive component are measured. And established the component's wide frequency equivalent circuit through vector fitting and network synthesis. Then build wide-band models of active components based on engineering measurements. Stray parameters of the valve tower are calculated by the finite element method. Finally, a single-port MMC electromagnetic transient model based on the wide frequency characteristics is established. By studying the electromagnetic interference of the valve during operation, it can be seen that the ideal model has a large deviation at high frequencies. The construction of the wide frequency model of the converter valve has great engineering significance for the simulation of electromagnetic interference.
Funding Information
  • SGCC (52130419000M,5200-201921062A-0-0-00)