Analysis of the Ionized Field Under HVDC Transmission Lines in the Presence of Wind Based on Upstream Finite Element Method
Authors:
- 19 July 2010
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Magnetics
- Vol. 46 (8) , 2939-2942
Abstract
Corona phenomenon generated from high voltage direct current (HVDC) transmission lines can affect the environment nearby. Based on the upstream finite element method, an iterative algorithm is used to analyze the ionized electric field and the ion current density at the ground level with the wind velocity taken into consideration. The algorithm is efficiently convergent. The proposed method is testified by measurement results of a unipolar line in the presence of wind and a bipolar test line. Finally some examples are analyzed to predict the effect of the wind and to determine the transmission corridor of ±800 kV HVDC transmission line.Keywords
This publication has 9 references indexed in Scilit:
- Analysis of the Electric Field and Ion Current Density Under Ultra High-Voltage Direct-Current Transmission Lines Based on Finite Element MethodIEEE Transactions on Magnetics, 2007
- A New Approach to Calculate the Ionized Field of HVDC Transmission Lines in the Space and on the Earth Surface2006
- Corona power loss, electric field, and current density profiles in bundled horizontal and vertical bipolar conductorsIEEE Transactions on Industry Applications, 2002
- A Very Stable Calculation Method for Ion Flow Field of HVDC Transmission LinesIEEE Transactions on Power Delivery, 1987
- Electric Fields and Ion Currents of a ±400 kV HVDC Test LineIEEE Transactions on Power Apparatus and Systems, 1983
- Influence of Wind and Conductor Potential on Distributions of Electric Field and Ion Current Density at Ground Level in DC High Voltage Line to Plane GeometryIEEE Transactions on Power Apparatus and Systems, 1982
- Calculation of ION Flow Fields of HVDC Transmission Lines By the Finite Element MethodIEEE Transactions on Power Apparatus and Systems, 1981
- Finite Element Solution for Electric Fields of Coronating DC Transmission LinesIEEE Transactions on Power Apparatus and Systems, 1979
- Analysis of Corona Losses on DC Transmission Lines: I - Unipolar LinesIEEE Transactions on Power Apparatus and Systems, 1969