The design of drilled shaft foundations can be based on ultimate load concepts, combined with suitable values of factor of safety, for cases where deflections of the foundations are of secondary interest. One example where deflection is not the controlling condition is for drilled shaft sound barrier walls foundations. This paper describes a simple and practical ultimate load design method for drilled shaft foundations. Field load tests were performed on 20 model drilled shaft foundations, 203 mm (8 inches) or 229 mm (9 inches) nominal diameter, at five sites in Virginia, where the foundation soils were partially saturated silts and clays. The results of these tests were used to examine the accuracy and reliability of the ultimate load theories developed by Broms (1964) and Brinch-Hansen (1961). It was found that Broms's theory provides an adequate method of analysis for drilled shafts in cohesionless soils, and Brinch-Hansen's theory provides a suitable method for soils with both cohesion and friction.