This paper deals with the performance analysis of a static compensator (STATCOM)-based voltage regulator for self-excited induction generators (SEIGs) supplying nonlinear loads. In practice, a number of loads are nonlinear in nature, and therefore, they inject harmonics in the generating systems. The SEIG's performance, being a weak isolated system, is very much affected by these harmonics. The additional drawbacks of the SEIG are poor voltage regulation and that it requires an adjustable reactive power source with varying loads to maintain a constant terminal voltage. A three-phase insulated-gate-bipolar-transistor-based current-controlled voltage source inverter working as STATCOM is used for harmonic elimination, and it provides the required reactive power for the SEIG, with varying loads to maintain a constant terminal voltage. A dynamic model of the SEIG-STATCOM feeding nonlinear loads using stationary d-q axes reference frame is developed for predicting the behavior of the system under transient conditions. The simulated results show that SEIG terminal voltage is maintained constant, even with nonlinear balanced and unbalanced loads, and free from harmonics using STATCOM-based voltage regulatorKeywords
This publication has 15 references indexed in Scilit:
- Analysis of isolated self-excited induction generator feeding a rectifier loadIEE Proceedings - Generation, Transmission and Distribution, 2002
- Transient performance of three-phase self-excited induction generator during balanced and unbalanced faultsIEE Proceedings - Generation, Transmission and Distribution, 2002
- Simple Control for a Wind-Driven Induction GeneratorIEEE Industry Applications Magazine, 2001
- Analysis of voltage control for a self-excited induction generator using a current-controlled voltage source inverter (CC-VSI)IEE Proceedings - Generation, Transmission and Distribution, 2001
- An alternative isolated wind electric pumping system using induction machinesIEEE Transactions on Energy Conversion, 1999
- Transient performance of an isolated induction generator under unbalanced excitation capacitorsIEEE Transactions on Energy Conversion, 1999
- Analysis of a novel solid state voltage regulator for a self-excited induction generatorIEE Proceedings - Generation, Transmission and Distribution, 1998
- Transient and steady-state load performanceof astand-alone self-excited induction generatorIEE Proceedings - Electric Power Applications, 1996
- Vector analysis and control of advanced static VAR compensatorsIEE Proceedings C Generation, Transmission and Distribution, 1993
- Static Exciters for Induction GeneratorsIEEE Transactions on Industry Applications, 1977