Formulas for predicting the dynamic performance of ROCOF relays for embedded generation applications
- 1 January 2006
- journal article
- Published by Institution of Engineering and Technology (IET) in IEE Proceedings - Generation, Transmission and Distribution
- Vol. 153 (4) , 399-406
Abstract
The paper presents a set of formulas for directly predicting the performance of rate-of-change-of-frequency (ROCOF) relays used to detect islanding of embedded synchronous generators. The formulas are analytically derived from the dynamic model of the generator and relay. Dynamic simulation results obtained using a representative distribution system confirm the validity and accuracy of the formulas. The formulas presented are a useful tool for protection engineers; they can be used, for example, to assess the effectiveness of anti-islanding schemes based on ROCOF relays, or to assist the selection of relay settings, significantly reducing the number of repeated dynamic simulations necessary to carry out such studies.Keywords
This publication has 3 references indexed in Scilit:
- An Open Source Power System Analysis ToolboxIEEE Transactions on Power Systems, 2005
- Comparative Analysis Between ROCOF and Vector Surge Relays for Distributed Generation ApplicationsIEEE Transactions on Power Delivery, 2005
- Performance of ROCOF relays for embedded generation applicationsIEE Proceedings - Generation, Transmission and Distribution, 2005