Reduction of active power losses in overhead power transmission lines rated for 6–35 kV

Authors:

Abstract
In order to ensure reliable and uninterrupted electric power supply for electric power users it is necessary to properly build an electric power supply system, and in particular to minimize electric power losses during its transmission from the generation source to the users. One of the solutions is to design the structure of uninsulated cables rated for 6-35 kV voltage class transmission with increased side surface, which allows increasing the rate of heat exchange between the cable and the environment. Comparative calculation of two wires variants showed reduction in thermal resistance values by 25% while increasing surface ribbing coefficient 40%, which in turn leads to lower of electrical power losses in line.