Abstract
DC-link voltage control is of great importance for modular multilevel converter (MMC)-based high-voltage directcurrent (HVDC) systems. Existing methods need to measure the actual DC-link voltage, which are referred to as direct control methods in this paper and require reliable DC voltage measuring device. The measurement system is complicated. And once malfunction occurs, DC-link voltage control may fail. This paper aims to develop an DC-link voltage control method without actual voltage measurement. The idea is based on the coupling effect between DC-link voltage and submodule (SM) capacitor voltage. Based on the analysis, an indirect DC-link voltage control method is proposed. In this method, the existing DC-link voltage control loop is first replaced by the total capacitor voltage regulation control loop. Then, a compensation signal is introduced to the switching functions to mitigate undesired voltage deviation. Two approaches are proposed to generate proper compensation signal. The proposed method can be integrated into existing MMC control system. And in measurement failure cases, it can come into service and continue maintaining MMC DC-link voltage, improving system reliability. Both simulation and experimental results confirm validity and effectiveness of the proposed method.

This publication has 41 references indexed in Scilit: