Decaying DC Offset Current Mitigation in Phasor Estimation Applications: A Review
Open Access
Abstract
Decaying DC (DDC) offset current mitigation is a vital challenge in phasor current estimation since it causes malfunctioning/maloperation of measurements and protection systems. Due to the inductive nature of electric power systems, the current during fault inception cannot change immediately and it contains a transient oscillation. The oscillatory component acts similar to an exponential DC signal and its characteristics depend on the X/R ratio of the system, fault location, and fault impedance. DDC attenuates accurate phasor estimation, which is pivotal in protection systems. Therefore, the DDC must be eliminated from the fault current (FC) signal. This paper presents an overview of DDC mitigation methods by considering different groups—before the discrete Fourier transform (pre-DFT), after the discrete Fourier transform (post-DFT), the least square-based (LS-based), and other methods. Through a comprehensive review of the existing schemes, the effects of noise, harmonics, multiple DDCs (MDDCs), and off-nominal frequency (ONF) on the accuracy of DDC estimation, were recognized. A detailed discussion (along with some simulation results) are presented to address the main advantages/disadvantages of the past studies. Finally, this paper presents a few suggestions for future researchers, for researchers to investigate more implementable solutions in this field.Keywords
This publication has 58 references indexed in Scilit:
- Stationary wavelet transform and single differentiator based decaying DC-offset filtering in post fault measurementsMeasurement, 2013
- Weighted least error squares based variable window phasor estimator for distance relaying applicationIET Generation, Transmission & Distribution, 2011
- A Discrete Fourier Transform-Based Adaptive Mimic Phasor Estimator for Distance Relaying ApplicationsIEEE Transactions on Power Delivery, 2006
- Removal of dc offset and subsynchronous resonance in current signals for series compensated transmission lines using a novel Fourier filter algorithmElectric Power Systems Research, 2006
- A new digital transformation for harmonics and DC offset removal for the distance fault locator algorithmInternational Journal of Electrical Power & Energy Systems, 2004
- Simplified algorithms for removal of the effect of exponentially decaying DC-offset on the fourier algorithmIEEE Transactions on Power Delivery, 2003
- Adaptive measuring algorithm suppressing a decaying DC component for digital protective relaysElectric Power Systems Research, 2001
- Removal of decaying DC in current and voltage signals using a modified Fourier filter algorithmIEEE Transactions on Power Delivery, 2001
- Removal of DC offset in current and voltage signals using a novel Fourier filter algorithmIEEE Transactions on Power Delivery, 2000
- Removal of DC-offset in current waveforms using digital mimic filteringIEEE Transactions on Power Delivery, 1995