Open-Switch Fault Tolerance Control for a Three-Level NPC/T-Type Rectifier in Wind Turbine Systems
Authors:
- 14 August 2014
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Industrial Electronics
- Vol. 62 (2) , 1012-1021
Abstract
Three-level topologies are widely used in back-to-back converters of wind turbine generation (WTG) systems. In comparison with a conventional two-level topology, three-level topologies have more advantages, particularly for the high power. Neutral-point clamped (NPC) and T-type are typical three-level topologies. An open-switch fault of a three-level rectifier that is connected to a permanent-magnet synchronous generator (PMSG) leads to the current distortion and torque vibration in WTG systems. Furthermore, WTG systems can break down in the worst case. Therefore, a tolerance control for open-switch faults is required to improve the reliability of WTG systems. WTG systems by applying the tolerance control can be stopped safely and prevent additional problems. Depending on the situation, it can keep the operation of WTG systems under open-switch fault. The effects of outer open-switch faults of three-level rectifiers are analyzed by considering PMSG specifications in this paper. Moreover, a tolerance control for outer open-switch faults of the NPC and T-type three-level rectifiers are proposed with existing tolerance controls for inner open-switch faults. The proposed tolerance control is to inject the exact $d$-axis current value to eliminate current distortion. The simulation and experiment are conducted to prove the feasibility of the proposed tolerance control and to identify its performance.Keywords
Funding Information
- Human Resources Development program of the Korea Institute of Energy Technology Evaluation and Planning (KETEP) (20134030200310)
- Korea government Ministry of Knowledge Economy
- Basic Science Research Program
- National Research Foundation of Korea
- Ministry of Education
This publication has 25 references indexed in Scilit:
- An Open-Switch Fault Detection Method and Tolerance Controls Based on SVM in a Grid-Connected T-Type Rectifier With Unity Power FactorIEEE Transactions on Industrial Electronics, 2014
- Diagnosis and Tolerant Strategy of an Open-Switch Fault for T-Type Three-Level Inverter SystemsIEEE Transactions on Industry Applications, 2013
- A Hybrid Five-Level Inverter With Common-Mode Voltage Elimination Having Single Voltage Source for IM Drive ApplicationsIEEE Transactions on Industry Applications, 2012
- Fault detection and tolerant control of 3-phase NPC active rectifier2012
- Diagnosis method of an open-switch fault for a grid-connected T-type three-level inverter system2012
- Use of Stored Energy in PMSG Rotor Inertia for Low-Voltage Ride-Through in Back-to-Back NPC Converter-Based Wind Power SystemsIEEE Transactions on Industrial Electronics, 2012
- Method for Detecting an Open-Switch Fault in a Grid-Connected NPC Inverter SystemIEEE Transactions on Power Electronics, 2011
- A Survey on Cascaded Multilevel InvertersIEEE Transactions on Industrial Electronics, 2009
- A Comparison of Three-Level Converters Versus Two-Level Converters for Low-Voltage Drives, Traction, and Utility ApplicationsIEEE Transactions on Industry Applications, 2005
- Reduced-parts-count multilevel rectifiersIEEE Transactions on Industrial Electronics, 2002