Abstract
The influence of nonuniform aging has not been considered in the prediction of the frequency domain spectroscopy (FDS) of the transformer oil-paper insulation (OPI) when using the finite element method (FEM). Given this issue, the modified simulation model was constructed based on the XY model and FEM. In the current work, the dielectric response property of the pressboards with different aging conditions in the modified model was characterized by its dielectric response parameters measured in the lab. Then the modified simulation model constructed in a 3-D system would be applied to study the effect of both nonuniform aging and the axial geometry on the FDS of OPI. Finally, the feasibility of the proposed models was verified by comparing the measured FDS and the predicted FDS. This article is expected to provide a model for predicting the FDS of the transformer OPI including the effect of nonuniform aging.
Funding Information
  • National Natural Science Foundation of China (52007036)
  • Visiting Scholarship of State Key Laboratory of Power Transmission Equipment & System Security and New Technology (2020-CQUKL- 408)
  • Natural Science Foundation of Guangxi (2018JJB160064)

This publication has 21 references indexed in Scilit: