Evaluation of controlled energisation of an unloaded power transformer for minimising the level of inrush current and transient voltage distortion using PIR‐CBs
Open Access
- 24 April 2018
- journal article
- research article
- Published by Institution of Engineering and Technology (IET) in IET Generation, Transmission & Distribution
- Vol. 12 (11) , 2788-2798
Abstract
This study presents an evaluation of the application of the controlled switching device for reducing the level of inrush current and transient voltage dip (TVD) during energisation of an unloaded power transformer using circuit breaker having pre‐insertion resistor (PIR‐CB). This evaluation is achieved by analysing the effect of statistical scatter of mechanical operating time (MOT), tolerance of auxiliary contact used as a feedback for a controlled switching device, and variation in mechanical insertion time (MIT) and electrical insertion time (EIT) of the PIR‐CB. The modelling of a complete system consisting of a power source, PIR‐CB, and two types of power transformers (electrically and magnetically coupled) is carried out using power systems computer‐aided design/electro‐magnetic transient design and control (PSCAD/EMTDC) software package. The results obtained from the simulations are compared with the results obtained during energisation of similar transformers in the real field. Finally, the performance of PIR‐CB‐based proposed methodology has been compared with the conventional methodology (non‐PIR‐CB) with reference to mitigation of inrush and TVD. The close match between field results and that obtained with simulation for both electrically and magnetically coupled transformers authenticate the proposed methodology.Keywords
This publication has 17 references indexed in Scilit:
- Mitigation of magnetic inrush current during controlled energization of coupled un-loaded power transformers in presence of residual flux without load side voltage measurementsInternational Journal of Electrical Power & Energy Systems, 2016
- Controlled Switching of a 1200 MVA Transformer in ManitobaIEEE Transactions on Power Delivery, 2016
- Power Testing of Preinsertion Resistors: Limitations and SolutionIEEE Transactions on Power Delivery, 2016
- Elimination of Residual Flux in Transformers by the Application of an Alternating Polarity DC Voltage SourceIEEE Transactions on Power Delivery, 2014
- Decision Tree based discrimination between inrush currents and internal faults in power transformerInternational Journal of Electrical Power & Energy Systems, 2011
- Controlled Switching of HVAC Circuit Breakers: Application Examples and Benefits2008
- Assessing and Limiting Impact of Transformer Inrush Current on Power QualityIEEE Transactions on Power Delivery, 2006
- Adaptive digital differential relay with overexcitation and inrush restraintElectric Power Systems Research, 1997
- Online identification of magnetizing inrush and internal faults in three-phase transformersIEEE Transactions on Power Delivery, 1992
- Elimination of closing resistors on EHV circuit breakersIEEE Transactions on Power Delivery, 1988